Duct CFM Calculator
Estimate total system airflow from tonnage (~400 CFM/ton) and a room's share of it by area.
Ductwork is sized around airflow, measured in CFM — cubic feet of air per minute. The starting rule for a residential system is about `400` CFM per ton of cooling capacity, so a `3`-ton system moves roughly `1,200` CFM total. Humid climates often design a little lower, near `350` CFM/ton, to give the coil more time to wring out moisture; dry climates run higher, near `450`.
Once you know total airflow, a first-pass way to split it among rooms is by floor area: a room gets the share of total CFM equal to its share of the conditioned square footage. A `150` square-foot bedroom in a `1,500` square-foot home is `10%` of the area, so it gets about `10%` of `1,200` CFM, or `120` CFM. That sets a target for the supply register and branch duct feeding that room.
This area split is a planning estimate, not a duct design. Real rooms differ in heat load — a west-facing room with big windows needs more air than a shaded interior room of the same size — so a proper job uses a room-by-room Manual J load calculation feeding a Manual D duct design, then balancing dampers to fine-tune. Use these numbers to sanity-check registers and spot rooms that are starved for air.
total airflow = 3 × 400 = `1,200 CFM` (`2,039 m³/h`)
room airflow = 1,200 × (150 ÷ 1,500) = `120 CFM`