Conduit Fill Calculator

See how many THHN conductors fit an EMT conduit at the NEC 40% fill limit, or check whether your pull passes — a planning estimate to confirm with a licensed electrician.

Your pull
wires
Results update as you type — no submit
ResultsLIVE
Max 12 AWG THHN at 40%
9 conductors
½ in EMT · 0.304 in² internal
Your 3-conductor pullFits ✓
Fill13.1% of conduit
Allowable fill40% (3+ wires)
Formula
allowable = 0.304 in² × 40% = 0.1216 in²
capacity (40%) = 0.1216 ÷ 0.0133 = 9 conductors

Conduit fill is an area problem. The NEC limits how much of a conduit's inside cross-section the conductors may occupy so the wires can be pulled without damage and can shed heat. This calculator compares the total area of your conductors against the allowable area of the conduit and tells you whether the pull passes, plus how many conductors of that size the conduit can hold. It reproduces published NEC tables and is meant for planning — a licensed electrician and your local code have the final word.

The fill percentage comes from NEC Chapter 9, Table 1: one conductor may fill up to `53%`, exactly two are limited to `31%`, and three or more may fill up to `40%`. The calculator picks the right percentage automatically from your conductor count. Conduit areas come from NEC Chapter 9, Table 4 — the tool covers EMT (electrical metallic tubing) from `1/2` inch through `2` inch. Individual conductor areas come from NEC Chapter 9, Table 5 for THHN/THWN, the most common building wire.

To find capacity, the calculator multiplies the conduit's internal area by the `40%` limit and divides by the area of one conductor, rounding down to a whole wire. To check a specific pull, it adds up the conductor areas and compares them with the allowable area. If you are over, step up a trade size or use a smaller conductor. Note that a bare or insulated equipment ground still counts as a conductor for fill.

Worked example
Conduit `1/2 in` EMT · conductor `12 AWG` THHN · pulling `3` wires
EMT `1/2 in` internal area = `0.304 in²` (NEC Table 4)
allowable at `40%` = `0.304` × `0.40` = `0.1216 in²`
`12 AWG` THHN area = `0.0133 in²` (NEC Table 5)
capacity = `0.1216` ÷ `0.0133` = `9.14` → `9` conductors, so `3` fits easily
For 12 AWG THHN in 1/2 inch EMT, the answer is 9 conductors at the 40% fill limit — the classic conduit-fill result. It comes from 0.304 in² of tubing times 40%, divided by the 0.0133 in² area of one 12 AWG THHN. Larger conductors or a different conduit type change the count, so always verify against the tables.
SOURCESFill % NEC Ch.9 Table 1 (53/31/40) · EMT areas NEC Ch.9 Table 4 · THHN/THWN conductor areas NEC Ch.9 Table 5
NEC-referenced estimate for planning only — electrical work must meet local code and be done or inspected by a licensed electrician; local code governs.